Commercial Rooftop Unit (RTU) Fall & Winter Maintenance Checklist for Connecticut Facilities

Oct 28
4 min read

Most commercial buildings in north-central Connecticut, from retail plazas in Enfield and Manchester to offices, schools, and light-industrial spaces in Vernon, Ellington, and the greater Hartford area, rely on packaged rooftop units (RTUs) to heat, cool, and ventilate. Those units spend the summer running hard in cooling mode, and then they are asked to switch to heating just as the weather turns against them.


A rooftop unit that skips its fall service doesn't always fail right away. More often it limps into December with a weak ignition sequence, a sticking economizer, or a partially blocked drain, and then fails on the coldest morning of the week. This checklist walks through what a proper fall and winter preventive maintenance visit should cover, so you know what to ask for and what to expect.


Why fall maintenance matters for rooftop units

RTUs live outdoors year-round. In our region they deal with freeze-thaw cycles, wind-driven snow, ice, and long stretches of heating demand. Fall is the window to catch problems while the unit is still accessible, the roof is clear, and a repair can be scheduled instead of handled as an emergency.


A good fall visit focuses on three things: safe, reliable heat, correct outdoor air control, and protecting the unit from winter conditions.


1. Gas heat section (gas/electric RTUs)

For gas-fired units, the heating section deserves the most attention because it involves combustion and occupant safety.


  • Inspect the heat exchanger for cracks, holes, rust-through, or signs of overheating.

  • Clean and inspect burners for rust, debris, insect nests, and proper alignment.

  • Check the ignitor and flame sensor; clean or replace the flame sensor as needed.

  • Verify the inducer (draft) motor, pressure switch, and flue/vent path are clear and working.

  • Confirm gas supply and manifold pressures against the manufacturer's data plate and installation instructions.

  • Perform a combustion check with an analyzer where applicable, and check for carbon monoxide around the unit and in the supply air.

  • Test all safety limits and rollout switches, and run the unit through a full call for heat.


2. Electric heat and heat pump RTUs

Not every rooftop unit burns gas. If your building uses electric heat strips or heat pump packaged units:


  • Check heater elements, sequencers, and limit switches; measure amp draw on each stage.

  • Inspect wiring and terminals for heat discoloration or loose connections.

  • On heat pumps, verify the reversing valve operation and the defrost control and sensors.

  • Confirm auxiliary or emergency heat stages engage when they should.


3. Economizer and outdoor air controls

The economizer is one of the most commonly neglected parts of an RTU, and in winter a malfunction can cost you comfort and energy.


  • Inspect outdoor and return air dampers for free movement, broken linkages, and worn seals.

  • Test the damper actuator through its full stroke.

  • Verify outdoor air, return air, and mixed or supply air sensors are reading correctly.

  • Confirm the minimum outdoor air position matches the building's ventilation requirements.

  • Check that the economizer closes to minimum when it should, so the unit isn't pulling in excess cold air.


A damper stuck open in January can overwhelm the heating section, create cold spots near the diffusers, and in some units contribute to freeze-stat trips.


4. Airflow: filters, belts, and blowers

Heating performance depends on moving the right amount of air across the heat exchanger or heating elements.


  • Replace filters and confirm the correct size and fit, with no gaps around the rack.

  • Inspect belts for cracking and glazing; check tension and pulley alignment.

  • Check blower bearings, wheel cleanliness, and motor amp draw.

  • Make sure supply and return paths aren't restricted by closed or blocked dampers.


5. Condensate drains and freeze protection

Drain problems are a classic winter headache on rooftops.


  • Clean the drain pan, trap, and line, and confirm proper slope and flow.

  • Check for cracked or sagging drain piping on the roof.

  • Where a unit has a history of freezing drains, discuss heat tape or other freeze protection with your technician.

  • On units with hydronic or steam coils, confirm freeze protection controls are installed and working.


6. Electrical and controls

  • Tighten electrical connections and inspect contactors, relays, and capacitors.

  • Check the disconnect and its weatherproof cover.

  • Verify thermostat or building automation system (BAS) schedules, setpoints, and occupied/unoccupied modes for the heating season.

  • Review any stored fault or alarm history on the unit controller and address recurring codes.


7. Cabinet, curb, and roof conditions

  • Confirm all access panels are in place, fastened, and properly gasketed.

  • Inspect the roof curb and curb seal for gaps that let in water or cold air.

  • Check outdoor air intake hoods and screens for debris, and make sure the bird screen is intact.

  • Note clearances around the unit so snow can be managed after storms. Intakes and flue outlets should never be buried in snow or ice.


What building owners and managers can do between visits

You don't need to go on the roof to help your RTUs through the winter. Pay attention to:


  • Hot and cold complaints in specific zones, which can point to a single unit.

  • Unusual noises, burning smells when the heat first starts, or frequent short cycling.

  • Snow accumulation after storms. Work with your snow removal vendor so rooftop equipment, intakes, and vents are kept clear and roof access is safe.

  • BAS or thermostat alarms that repeat. Repeated alarms are a reason to schedule service, not to keep resetting the unit.


If anything seems off, it is almost always less disruptive to schedule a service call than to wait for a no-heat call on a weekend.


Commercial RTU service in north-central Connecticut

i-HVACR is a commercial-only HVACR service company based in Ellington, CT. We service rooftop units, VRF systems, and other commercial HVAC and refrigeration equipment for businesses, property managers, and facilities across Hartford and Tolland counties, including Ellington, Manchester, Vernon, Enfield, and the surrounding area.


If your rooftop units haven't had their fall service yet, or you'd like a preventive maintenance plan built around your building's equipment, call us at 844-448-2272 or use the contact form on our website to schedule a visit.


 
 
 

Recent Posts

See All

Comments


Connect with i-HVACR:
Phone - 844-448-2272
General email info@i-hvacr.com

Physical address 408 Somers Rd. Unit B, Ellington, CT 06029

Mailing address 111 Sheldon Rd., PO Box 2241, Manchester, CT 06045

Subscribe to Our Newsletter

Stay Connected

  • Facebook
  • Instagram
  • LinkedIn
  • X

© 2018-2026 by i-HVACR. All rights reserved.

bottom of page